qaaf

Cable Size Calculator: 7/29, 3/29 and mm² Wire Sizes

The copper wire size for your load in mm² and in Pakistani strand sizes like 3/29, 7/29 and 7/44, with the breaker to match. Single phase 230 V or three phase 400 V, rated to BS 7671.
Supply
Load is in
m

From the breaker or meter to the load, measured along the route.

Use 1 for heaters and geysers, 0.8 for motors, pumps and AC units.

How the wire is run

Summer heat lowers what a cable can carry. Roofs and outer walls in the plains often pass 40°C.

%

3% for lighting circuits, 5% for sockets, motors and other loads, counted from the meter.

Cable sizesingle phase 230 V
Minimum copper wire on a 16 A breaker
7/.029or 2.5 mm²
Design current 2,500 W ÷ (230 V × 0.8)13.6 A
Breaker smallest standard size at or above 13.6 A16 A MCB
Derating 40°C × 0.87, no grouping × 1.000.87
Table rating needed 16 A ÷ 0.87, conduit, 2 cables18.4 A
Size by current 2.5 mm² is rated 24 A, 1.5 mm² only 17.5 A2.5 mm²
Size by voltage drop 5% of 230 V = 11.5 V, so at most 33.86 mV/A/m over 25 m1.5 mm²
Voltage drop on 2.5 mm² 18 × 13.6 A × 25 m ÷ 10006.1 V (2.7%)
Metric size needed set by current; rated 20.9 A here2.5 mm²
Pakistani size 7/.029 has 2.98 mm² of copper, rated about 23.1 A here, drop 2.3%7/.029

Copper, single-core PVC wires to BS 7671 Table 4D1A. A licensed electrician must check the final choice against your wiring, earthing and breaker before the circuit is switched on.

7/29 wire is seven copper strands, each 0.029 inch (0.737 mm) thick, which makes 2.98 mm² of copper. Shops sell it against the 2.5 mm² metric size. In conduit on a single-phase circuit it carries about 26.6 A at 30°C and 23.1 A at 40°C, so in a Pakistani summer it suits a 20 A breaker. 3/29 has only 1.28 mm² of copper, less than the 1.5 mm² it is sold against.

The calculator works out the current your load draws, picks the breaker, applies heat and grouping factors, then checks voltage drop over your cable length. It gives the smallest metric size and the smallest Pakistani strand size that pass both checks, with every step shown.

Cable size chart: Pakistani wire sizes in mm and amps

Copper wires with PVC insulation, as sold in 90 m coils. Amps are the BS 7671 table ratings at 30°C air. The last column applies the 40°C factor (0.87) and gives the largest standard breaker the wire can sit behind.

WireStrandCopper (mm²)Sold asConduit, 1 phase (A)Conduit, 3 phase (A)Clipped, 1 phase (A)Drop 1 phase (mV/A/m)Largest MCB, conduit 1 phase at 40°C
3/.0290.737 mm1.281.5 mm²15.713.91835.613 A
7/.0290.737 mm2.982.5 mm²26.623.330.215.720 A
7/.0360.914 mm4.604 mm²34.730.4409.925 A
7/.0441.118 mm6.876 mm²44.53950.96.732 A
7/.0521.321 mm9.5910 mm²55.448.663.24.740 A
7/.0641.626 mm14.5316 mm²71.363.681.63.250 A
19/.0521.321 mm26.0325 mm²103.591.2116.81.780 A
19/.0641.626 mm39.4335 mm²132.7117.1153.11.2100 A
19/.0832.108 mm66.3270 mm²184.5164.2224.40.8125 A

Imperial wires are rated from their real copper area, in a straight line between the two nearest metric sizes in the BS 7671 table. That never gives a wire more than the table would. Drop is the voltage lost per amp per metre of run on a single-phase circuit.

What 3/29, 7/29 and 7/44 mean

Pakistani house wire is named by the number of strands and the thickness of each strand in inches. 7/.029 (said as seven by twenty-nine) is 7 strands of 0.029 inch. The copper area is the number of strands times the area of one strand:

  1. Strand diameter: 0.029 x 25.4 = 0.737 mm.
  2. Area of one strand: 3.1416 ÷ 4 x 0.737 x 0.737 = 0.426 mm².
  3. Seven strands: 7 x 0.426 = 2.98 mm².

The same sum gives 1.28 mm² for 3/29, 4.60 mm² for 7/36, 6.87 mm² for 7/44, 9.59 mm² for 7/52 and 14.53 mm² for 7/64. Makers label these as 1.5, 4, 6, 10 and 16 mm². Most are close, but 3/29 and 7/64 carry noticeably less copper than their labels, which is why the calculator rates them by their own area.

Which wire goes where in a house

In most Pakistani homes, lights and fans run on 3/29, socket circuits on 7/29, a 1.5 ton AC or water motor on 7/36, and a 2 ton AC or instant geyser on 7/44. The supply from the meter to the main board is usually 7/52 or 7/64. These are habits, not rules: the size you need depends on the breaker, the heat and the length of the run.

Electrical cable size chart in amps (mm²)

Single-core copper PVC cables, BS 7671 Table 4D1A and 4D1B. Conduit means reference method B, clipped means reference method C. Single phase is 2 loaded cables, three phase is 3 or 4.

SizeConduit, 1 phase (A)Conduit, 3 phase (A)Clipped, 1 phase (A)Clipped, 3 phase (A)Drop 1 phase (mV/A/m)Drop 3 phase (mV/A/m)Largest MCB, conduit 1 phase at 40°C
1 mm²13.51215.5144438.110 A
1.5 mm²17.515.52018292513 A
2.5 mm²24212725181520 A
4 mm²32283733119.525 A
6 mm²413647437.36.432 A
10 mm²575065594.43.840 A
16 mm²766887792.82.463 A
25 mm²101891141041.81.5680 A
35 mm²1251101411291.31.13100 A
50 mm²15113418216710.87125 A
70 mm²1921712342140.720.63125 A
95 mm²2322072842610.560.49125 A

Ratings fall in heat: multiply by 0.94 at 35°C, 0.87 at 40°C, 0.79 at 45°C and 0.71 at 50°C. With 2 circuits in one conduit multiply by 0.80, with 3 by 0.70 and with 4 by 0.65.

How to calculate cable size

  1. Current. Single phase: watts ÷ (230 x power factor). Three phase: watts ÷ (1.732 x 400 x power factor). Use 1 for heaters and 0.8 for motors and AC units if you do not know it.
  2. Breaker. Take the next standard size at or above that current: 6, 10, 13, 16, 20, 25, 32, 40, 50, 63 A and so on.
  3. Derate. Divide the breaker rating by the temperature factor and the grouping factor. The answer is the table rating the cable needs.
  4. Size by current. Pick the smallest cable whose table rating is at least that figure.
  5. Voltage drop. Multiply the cable's mV/A/m by the current and the one-way length in metres, then divide by 1,000. Keep it within 3% for lighting (6.9 V on 230 V) and 5% for other circuits (11.5 V on 230 V, 20 V on 400 V).
  6. Take the bigger of the two sizes.

Worked examples

A 2,500 W circuit in conduit

Single phase, power factor 0.8, 25 m from the board, 40°C.

  1. Current: 2,500 ÷ (230 x 0.8) = 13.6 A, so a 16 A breaker.
  2. Table rating needed: 16 ÷ 0.87 = 18.4 A. 1.5 mm² is rated 17.5 A, too little; 2.5 mm² is rated 24 A.
  3. Drop on 2.5 mm²: 18 x 13.6 x 25 ÷ 1,000 = 6.1 V, or 2.7%.

Answer: 2.5 mm² or 7/29. 7/29 is rated about 26.6 A in the table and 23.1 A after the heat factor.

A 15 kW three-phase shop load

400 V, power factor 0.8, 40 m, clipped to the wall, 40°C.

  1. Current: 15,000 ÷ (1.732 x 400 x 0.8) = 27.1 A per phase, so a 32 A breaker.
  2. Table rating needed: 32 ÷ 0.87 = 36.8 A. 4 mm² is rated 33 A; 6 mm² is rated 43 A.
  3. Drop on 6 mm²: 6.4 x 27.1 x 40 ÷ 1,000 = 6.9 V, or 1.7% of 400 V.

Answer: 6 mm² or 7/44. 7/36 falls just short at about 36.0 A.

A long run where voltage drop decides

A 3,000 W heater, power factor 1, 60 m away, in conduit at 40°C. The current is 13.0 A and the breaker 16 A, so 2.5 mm² passes on current. But 5% of 230 V over 60 m allows only 14.7 mV/A/m, and 2.5 mm² drops 18. The answer moves up to 4 mm² or 7/36, which loses 8.6 V (3.7%) on 4 mm².

A licensed electrician must confirm the final wire and breaker before the circuit is switched on. These figures cover copper single-core PVC wires only. They do not cover earthing, loose joints, cheap undersized wire or a breaker that does not match the cable. For the load of a whole house, add up your appliances in the solar load calculator first.

Cable size questions

What is 7/29 wire size in mm?

7/29 is 7 strands of 0.029 inch, or 0.737 mm, copper. That is 2.98 mm² of copper, and it is sold as the 2.5 mm² equivalent. In conduit on a single-phase circuit it is rated about 26.6 A at 30°C, or 23.1 A in 40°C summer air, enough for a 20 A breaker.

What is 3/29 wire size in mm?

3/29 is 3 strands of 0.737 mm copper, which is 1.28 mm². Shops call it the 1.5 mm² size, but it has about 15% less copper. In conduit it is rated about 15.7 A at 30°C and 13.7 A at 40°C, so it suits a 10 A or 13 A breaker for lights and fans.

How do I choose a 3 phase cable size?

Divide the load in watts by 1.732 x 400 x power factor to get the current in each phase. Pick the next breaker size, divide it by the heat factor, and choose the cable from the three-phase column. Then check voltage drop against 5% of 400 V, which is 20 V. A 15 kW load at 0.8 power factor draws 27.1 A and needs 6 mm² or 7/44 at 40°C.

Which wire size for a 20 A or 32 A breaker?

Choose the wire by the breaker, not only by the appliance. In conduit at 40°C, a 20 A breaker needs a table rating of 23.0 A, so 2.5 mm² or 7/29. A 32 A breaker needs 36.8 A, so 6 mm² or 7/44 on a single-phase circuit. A long run may need one size larger for voltage drop.

Why does heat change the cable size?

Cable ratings are worked out for 30°C air. PVC insulation must stay at or below 70°C, so in hotter air the wire can take less current before it overheats. At 40°C a cable carries 87% of its table rating, and at 50°C only 71%. Wires bunched in one conduit also heat each other, so two circuits together carry 80%.

How do I calculate voltage drop in a cable?

Multiply the cable's mV/A/m figure by the current in amps and the one-way length in metres, then divide by 1,000 to get volts. For 2.5 mm² (18 mV/A/m) carrying 13.6 A over 25 m, that is 6.1 V, or 2.7% of 230 V. Keep lighting within 3% and other circuits within 5%.

Sources: Current ratings and voltage drop: BS 7671:2018 Requirements for Electrical Installations (IET Wiring Regulations, 18th edition), Appendix 4, Tables 4D1A and 4D1B, single-core 70°C thermoplastic copper cables, ambient 30°C; the same ratings appear in IEC 60364-5-52 Annex B. Temperature and grouping factors: IEC 60364-5-52 Tables B.52.14 and B.52.17. Breaker sizes: BS EN 60898-1 preferred rated currents. Breaker and cable rule: BS 7671 Regulation 433.1.1. Voltage drop limits: BS 7671 Appendix 4 and IEC 60364-5-52 Annex G. Supply voltage: NEPRA Distribution Code 2005, DPC 3.4 (400/230 V). Power factor guide: Schneider Electric Electrical Installation Guide. Strand sizes: Pakistan Cables and Fast Cables price lists for 250/440 V imperial wires; metric equivalents as labelled by Unicore Cables and Azmat Cables. Typical uses of each size: Pakistani cable sellers' size charts.

Last reviewed 1 October 2026. Results are estimates; official notices always take precedence.