qaafPakistan calculators

UPS Battery Backup Calculator

How long a UPS or inverter will run your fans and lights on its batteries, or which battery you need for the hours of load shedding you get. Tubular and lithium.
Question

What runs on the UPS

W

Add the watts of other appliances from their rating plates.

Battery

Battery type
Ah
V

Small home UPS units run on 12 V (one battery), bigger ones on 24 V or 48 V.

Efficiency and depth of discharge
%

Most home units 70% to 90%.

%

Usual for tubular lead-acid: 50%.

Many tubular batteries are rated at the 20-hour rate (C20) and some at the 10-hour rate (C10). Check the label and pick the same in the calculator.

UPS backup time298 W load
Backup time
2 hr 20 min
Battery energy 1 × 12 V × 185 Ah2.22 kWh
Usable 50% depth of discharge1.11 kWh
Power drawn from the battery373 W 298 W ÷ 80%
Current at 12 V31.0 A
Simple estimate, ignoring high-load losses2 hr 59 min
Backup after Peukert correction2 hr 20 min

Old batteries hold less. A battery at the end of its life may give half this time.

Backup time in hours is roughly battery volts x amp-hours x usable share x UPS efficiency ÷ load in watts. A 12 V 185 Ah tubular battery holds 2.22 kWh. Using half of it through an 80% efficient UPS, it runs a 298 W load for about 3 hours by that simple formula.

Lead-acid batteries give less than that when the load is heavy, so the calculator also applies Peukert's law. For the same example it gives 2 hours 20 minutes, which is closer to what people see at home. Switch to What battery do I need? to size a battery for your load-shedding hours.

Backup time for common battery setups

At 80% UPS efficiency, using 50% of a tubular battery and 90% of a lithium one. Tubular figures include the Peukert correction for a C20-rated battery.

Load12 V 185 Ah tubular2 × 12 V 185 Ah tubular25.6 V 100 Ah lithium51.2 V 100 Ah lithium
100 W8 hr 40 min17 hr 46 min18 hr 26 min36 hr 52 min
200 W3 hr 46 min8 hr 40 min9 hr 13 min18 hr 26 min
300 W2 hr 19 min5 hr 20 min6 hr 9 min12 hr 17 min
500 W1 hr 15 min2 hr 53 min3 hr 41 min7 hr 22 min
800 W43 min1 hr 39 min2 hr 18 min4 hr 36 min
1,000 W33 min1 hr 15 min1 hr 51 min3 hr 41 min

Two tubular batteries on a 24 V UPS last more than twice as long as one on a 12 V UPS, because each battery carries half the current and lead-acid loses less capacity at lower currents.

Worked example: fans, lights, TV and router

The calculator opens with 2 ceiling fans (80 W each), 4 LED bulbs (12 W each), a Wi-Fi router (10 W) and an LED TV (80 W): 298 W in all. The battery is one 12 V 185 Ah tubular on a 12 V UPS.

  1. Battery energy: 12 x 185 = 2,220 Wh.
  2. Power the UPS takes from the battery: 298 ÷ 0.80 = 372.5 W, so the current is 372.5 ÷ 12 = 31.0 A.
  3. Simple estimate: 2,220 x 50% ÷ 372.5 = 2.98 hours.
  4. Peukert correction: the battery is rated over 20 hours, which means 9.25 A. At 31 A it gives only 20 x (185 ÷ (31.0 x 20))^1.2 = 4.68 hours to empty. Half of that is 2 hours 20 minutes.

With two of these batteries on a 24 V UPS, the same load runs for about 5 hours 22 minutes. For 4 hours from a 12 V UPS you need about 289 Ah, so two 185 Ah batteries in parallel. A single 25.6 V 100 Ah lithium battery on a 24 V UPS runs the same load for about 6 hours 11 minutes.

What the settings mean

Depth of discharge

This is how much of the battery you use before the UPS cuts off. Tubular lead-acid batteries last the most years when drained to about half; sellers quote cycle life at up to 80%. Lithium (LiFePO4) batteries are normally used to 80% to 90%, which is why a smaller lithium battery can match a bigger tubular one.

UPS efficiency

The UPS turns 12 V or 24 V DC into 220 V AC and loses some energy doing it, more at very light loads. Most home units manage 70% to 90%.

C20 or C10

A battery's Ah is measured over a set time. A 185 Ah battery at the 20-hour rate (C20) gives 9.25 A for 20 hours. Drawn faster, it gives fewer amp-hours; Peukert's law with an exponent of 1.2 estimates by how much. Check your battery's label for its rating hours.

System voltage

Small home UPS units run on one 12 V battery. Bigger units need two 12 V batteries in series for 24 V, and solar inverters often use 48 V. Batteries in series add their volts; batteries in parallel add their amp-hours.

Figures are estimates for a healthy battery at room temperature. An old battery can give half its original backup. Charging the battery back up also takes units from your bill, more than the UPS delivered; the electricity usage calculator can add those losses. For backup from solar panels, use the solar system calculator.

UPS backup questions

How do I calculate UPS backup time?

Multiply battery volts by amp-hours by the number of batteries to get watt-hours. Multiply by the share you will use (50% for tubular, 90% for lithium) and by the UPS efficiency, then divide by the load in watts. For lead-acid at heavy loads, reduce the answer further; the calculator does this with Peukert's law.

How long will a 150 Ah battery run a fan?

A 12 V 150 Ah tubular battery holds 1,800 Wh. One 80 W ceiling fan through an 80% efficient UPS draws 100 W from the battery. Using half the battery, that is about 9 hours by the simple formula, and a little less with the Peukert correction. A DC inverter fan at 35 W lasts more than twice as long.

Which battery size do I need for 4 hours of backup?

It depends on the load. For 300 W on a 12 V UPS you need about 290 Ah of tubular battery, which in practice means two 185 Ah batteries. Enter your appliances, choose What battery do I need? and set 4 hours.

Is lithium better than tubular for a UPS?

Lithium (LiFePO4) lets you use about 90% of its capacity, keeps its capacity at high loads, lasts more cycles and charges faster. It costs more up front. A tubular battery is cheaper but should only be drained to about half, so it needs nearly twice the rated capacity for the same backup.

Can I run a fridge or AC on a UPS?

A small inverter fridge can run on a UPS rated for its starting surge, which can be several times its running watts. An AC needs a large inverter and a big battery bank: a 1 ton inverter AC at 700 W would drain a 12 V 185 Ah tubular battery in well under an hour.

Sources: Battery energy and Peukert's law: standard battery engineering. Depth of discharge and cycle life: battery makers' and sellers' specifications in Pakistan, September 2026. Appliance watts: typical figures used across our electricity calculators.

Last reviewed 30 September 2026. Results are estimates; official notices always take precedence.